Perform a Ramping Pickup Test via the Human Machine Interface (HMI)

Topic

Perform a Ramping Pickup Test via the Human Machine Interface (HMI)

These videos will show you different techniques for ramping pickup tests on a variety of relays that will not require you to change settings.

Valence Electrical Training Services is not endorsed, sponsored, or affiliated with any company, trademark, or owner of any trademarks presented in these videos. This material is intended for educational and informational purposes only and any use falls under the Fair Use Doctrine of Section 107 of the Copyright Act.

Click Here if You are testing an SEL Relay

The first video is unique to SEL relays via a TAR command with a terminal program. This is the method I use most often when testing SEL relays.

 

This video shows you how to test pickup on SEL relays using Quickset software and/or the front panel.

Click Here if You are testing a General Electric / GE / Multilin Relay

This video shows you how to test pickup on GE/Multilin SR relays using software and/or the front panel.

 

This video shows you how to test pickup on GE/Multilin UR relays using software and/or the front panel.

 

Click Here if You are testing a Beckwith Electric Relay

This video shows you how to test pickup on Beckwith Electric relays using software and/or the front panel.

 

Click Here if You are testing a Siemens Relay

This video shows you how to test pickup on Siemens relays using software and/or the front panel.

 

Click Here if You are testing an ABB Relay

This video shows you how to test pickup on ABB relays using software and/or the front panel.

 

Click Here if You Want to See More Videos About This Topic


Click “Mark Complete” below after watching the video so you can keep track of your progress.

8 Comments
Collapse Comments
Rune (Group Leader) May 23, 2017 at 3:01 pm

Hey Chris,

The video description says you will show how to test pickup on a Beckwith relay but then you show how to test automatic ramp pickup with the Manta on a SEL relay. Was there a mistake in the videos description?

Chris Werstiuk (Administrator) May 23, 2017 at 5:38 pm

Thanks for the heads-up.

Should be all fixed now.

Do you have example using Alstom/GE Micom relay or Schneider Micom relay ?
We have a utility that mainly using those type of relay.

Chris Werstiuk (Administrator) January 13, 2021 at 1:43 pm

We don’t have an example of any Micom relays yet.

Are you talking about a modern one, or an old-school k-series?

Do you know a rep in the US I can contact?

What model would be a good feeder relay example?

Joshua Liuga Suiramo March 4, 2021 at 11:01 am

When talking about ” forward fault and reverse fault” :
1. How do the relay determines it is a fault in ” forward or reverse directions?
2. What is the CT connections like for” forward fault and reverse fault”?

Thanks
Joshua

Yudhvir Rajpaulsingh August 3, 2022 at 8:16 pm

Chris,

Is the DIGSI software for Siemens Relays only available for purchase?

Chris Werstiuk (Administrator) August 4, 2022 at 10:33 pm

There is some dispute over that. It reads on the website like it is purchase only, but may people say you can download the software and use a free version.

I’m not sure because the license someone in the 90s gave me still works.

You can check out the comments in https://valence.relaytraining.com/topic/topic-s1-5-01-upload-sel-relay-settings/ and see if they still work.